History Industry
Model V Series Positioner Newsletter
Maintenance Manual Contact
Valve Related Controls


Performance

[ features | options | construction | dimensional diagrams | ordering| hazardous locations ]

Parameter

Specification

Resolution

0.25% Maximum
0.10% Typical

Repeatability

99.75% Minimum
99.90% Typical

Hysteresis

0.50% Maximum
0.25% Typical

Linearity

1.0% Maximum

Gain @80 PSIG

250 Single Acting
500 Double Acting

Air Consumption @80 PSIG

0.25 SCFM. Standard Flow Spool Valve

0.45 SCFM. Maximum Flow Spool Valve

Temp. Range

-40 to 150F/-40 to 65C